DEFLECTION
ACCESSORIES
COUPLERS
DEFLECTION
Unistru’s load and deflection are in accordance with CEVIEC 61537:2001, with the characteristic deflection of unistrut Cable Tray limited o span/100.
ACCESSORIES
To ensure adequate support, accessories should be supported locally
COUPLERS
The loading and deflection tables for Unistrut able Tray assume that the couplers ae located at the must onerous. position within the span (2. mid span).
To maintain the load deflection, the Couplers should not be located in end spans or over support locations Straight couplers were utilized for the testing of the medium an heavy duty cable trays. Only one par of couplers should be installed per span.
Note: Please follow manufacturer datasheets and guidelines for cable usage and installation.